The M Series and DAM Series Modbus Remote I/O Module
are industrial class, high reliability, high stability and high precision data
acquisition module, embedded 32-Bit High Performance Microprocessor MCU, it
provides 1 RS485 interface. It provides multi I/O, supports standard Modbus RTU,
can be intergraded into SCADA, OPC server, HMI and other automation systems. It
is design for working in the harsh industrial application environment, widely
used in a variety of industrial automation. More Details Please click this link DAM Series IO Module M Series Remote IO Module
More Details
Please click this link DAM Series IO Module M Series Remote IO Module
M Series Modbus Remote I/O Module Table
|
Model
|
Descriptions
|
DC
Output
|
DC
Input
|
Link
|
M100
|
1 RS485, 2 DI, 2 AI, 2 DO(Sink) or Relay
|
1 DC
|
12~36VDC
|
Details
|
M110
|
1 RS485, 4 DI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M120
|
1 RS485, 4 DI, 4 AI, 2AO, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M130
|
1 RS485, 8 DI, 4 DO(Sink) or Relay
|
1 DC
|
12~36VDC
|
Details
|
M140
|
1 RS485, 8 DI, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M150
|
1 RS485, 8 DI, 4 AI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M160
|
1 RS485, 8 DI, 8 AI, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M200
|
1 RS485, 2AO
|
1 DC
|
12~36VDC
|
Details
|
M210
|
1 RS485, 4 DI
|
1 DC
|
Details
|
M220
|
1 RS485, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M230
|
1 RS485, 4 AI
|
1 DC
|
Details
|
M240
|
1 RS485, 4 RTD, 2/3 wire PT100/pt1000
|
---
|
Details
|
M310
|
1 RS485, 8 DI
|
1 DC
|
12~36VDC
|
Details
|
M320
|
1 RS485, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M330
|
1 RS485, 8 AI
|
1 DC
|
Details
|
M340
|
1 RS485, 8 RTD, 2/3 wire PT100/pt1000
|
---
|
12~36VDC
|
Details
|
M410
|
1 RS485, 16 DI
|
1 DC
|
Details
|
M420
|
1 RS485, 16 DO(Sink) or Relay
|
---
|
Details
|
Notices
|
1.
If the
model provides digital input, the DIN default type: wet contact, optional:
dry contact. The input type cannot be changed after manufacturer delivered.
The DIN1 default is high-speed count mode, the counter frequency Max. is
10Mhz; it can be changed to low-speed count mode by open the shell and change
the internal jumper. If require dry contact input, please note when ordering,
if DIN1 require high-speed pulse count mode then must be wet contact.
2.
If the
model provides digital output, the DO default type: SINK, pulse output
frequency is 10Hz~300Khz. optional: Relay. The output type cannot be changed
after manufacturer delivered. The DO1 supports PWM high-speed pulse output,
the output duty cycle from 10-90%; DO2 can be used to control the direction
of the stepper motor. If require relay output, please note when ordering, if
DO1, DO2 used for high-speed pulse output then must be Sink.
3.
The
model number: M240T, M340T support thermal resistance temperature transmitter
default type: PT100, optional: PT1000, if you need PT1000 type of thermal
resistance, please note when ordering.
4.
The
valid number of I / O ports corresponding to the model number is described in
the Model List, the not included I/O port in the model label is invalid,
although in the hardware reserved them.
|
DAM Series Modbus Remote I/O Module Table
|
Model
|
Descriptions
|
DC
Output
|
DC
Input
|
Link
|
DAM102
|
1 RS485, 2 DI
|
1 DC
|
9~36VDC
|
Details
|
DAM108
|
1 RS485, 4 DI
|
1 DC
|
Details
|
DAM104
|
1 RS485, 2 Relay Outputs
|
1 DC
|
Details
|
DAM110
|
1 RS485, 4 Relay Outputs
|
1 DC
|
Details
|
DAM106
|
1 RS485, 2 DI , 2 Relay Outputs
|
1 DC
|
Details
|
DAM112
|
1 RS485, 4 DI , 4 Relay Outputs
|
1 DC
|
Details
|
DAM114
|
1 RS485, 2 AI
|
1 DC
|
Details
|
DAM116
|
1 RS485, 4 AI
|
1 DC
|
Details
|
DAM118
|
1 RS485, 2 RTD, 2/3 wire PT100/pt1000
|
1 DC
|
Details
|
DAM120
|
1 RS485, 4 RTD, 2/3 wire PT100/pt1000
|
1 DC
|
Details
|
DAM122
|
1 RS485, 2 AI, 4 RTD, 2/3 wire PT100/pt1000
|
1 DC
|
Details
|
DAM124
|
1 RS485, 4 AI, 4 RTD, 2/3 wire PT100/pt1000
|
1 DC
|
Details
|
DAM140
|
1 RS485, 16 AI
|
---
|
10-30VDC
|
Details
|
DAM142
|
1 RS485, 24 DI
|
---
|
Details
|
DAM144
|
1 RS485, 24 DO
|
---
|
Details
|
DAM400
|
1 RS485, 1-Ch Frequency measurement
module
|
---
|
8-30VDC
|
Details
|
DAM402
|
1 RS485, 2-Ch Frequency measurement
module
|
---
|
Details
|
Notice
|
1.
Analog
inputs supports 0~20mA/4~20mA/0-5V/0~10V, default is 4-20mA;
2.
DAM102~124
size : 70*88*30mm, DIN35mm RAIL bracket
is optional.
3.
RTD
inputs default is PT100, optional: PT1000.
|
|